MOORE SIGNAL TRANSMITTERS, ISOLATORS AND CONVERTERS

Convert, isolate, split, boost, and step down process signals so field instruments can interface directly with indicators, recorders, DCS, PLC, and PC-based SCADA systems.

Featured Interface Solutions

Unit

Input

Output

Power

Mounting

Features

SSX 2-Wire, Loop-Powered HART Safety Series Isolators

SSX Safety HART Signal Isolator Moore Industries

exida SIL3 Logo Moore Industries

 

Get Product Information and Installation Tools

Get exida SIL 3 Certificate

4-20mA
4-20mA into 100 ohms with HART digital data superimposed
1-5V into 1Mohm
Isolates Loop, Lets HART Digital Signal "Pass Through"
4-20mA Isolated,
4-20mA into 600 ohms (with 24Vdc power); with HART digital data superimposed
2-Wire,
Loop-Powered
12-42DC
DINUniversal DIN-style housing mounts on 32mm G-type rail (EN50035) or 35mm Top Hat rail (EN50022)

FLB Flange bracket with top/bottom mounting holes

exida certified
IEC 61508:2010
SIL 3 capable

Isolates the analog loop, and lets the HART digital signal pass through unaffected

Unit 

Input

Output

Power

Mounting

Features

SST 4-Wire, Line-(Mains) Powered HART Safety Series Isolator and Splitter

SST Safety HART Signal Isolator and Splitter Moore Industries

exida SIL3 Logo Moore Industries

 

Get Product Information and Installation Tools

Get exida SIL 3 Certificate

4-20mA
4-20mA into 100 ohms with HART digital data superimposed
1-5V into 1Mohm
Isolates Loop, Lets HART Digital Signal "Pass Through"
4-20mA Isolated,
4-20mA into 1000 ohms (with 24Vdc, 117Vac, or 230Vac power); with HART digital data superimposed 2x4-20mA into 600 ohms per channel (available with 4-20mA input only); HART digital data superimposed on Channel A only
4-Wire,
Line-Powered
24DC±10%
117AC50/60HZ,
±10%
230AC50/60HZ,
±10%
3 watts maximum for single channel models; 5 watts maximum for dual output channel models
DINUniversal DIN-style housing mounts on 32mm G-type rail (EN50035) or 35mm Top Hat rail (EN50022)

FLB Flange bracket with top/bottom mounting holes

exida certified
IEC 61508:2010
SIL 3 capable

Isolate and pass critical HART data

HART Splitter:
“Sharing” or
“Splitting” process
signals

Transmitter excitation: power a 2-wire transmitter

Unit 

Input

Output

Power

Mounting

Features

ECT-DIN 2- and 4-Wire Signal Isolators, Converters, Repeaters, and Splitters

ECT-DIN Signal Isolators Conveters Repeaters and Splitters in Metal Housings Moore Industries

 

Get Product Information and Installation Tools
4-20mA
1-5Vdc
0-150Vac
0-5Aac
4-20mA
Dual Output Channels for Signal Splitting

 

2-Wire,
Output Loop-Powered
(10-42Vdc)

2-Wire,
Input Loop-Powered
(5.5 volts loop-powered)

4-Wire,
Line-Powered
(24Vdc, 117Vac, or 230Vac)

High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)

Our most popular signal conditioner family

Fixed input and output types

1- and 2-channel configurations

Single input with dual outputs for signal splitting

Powers a 2-wire transmitter (transmitter excitation)

Unit 

Input

Output

Power

Mounting

Features

MIX and MIT miniMoore 2-Wire and 4-Wire Multi-Channel Signal Isolators and Converters

MIX Muliti-Channel Signal Isolators and Converters Moore Industries

 

Get Product Information and Installation Tools
Switch Selectable on 2-Channel Models
4-20mA
0-5V
1-5V
0-10V

Fixed 4-20mA input/4-20mA Output on 4-Channel MIX Models

Two (MIX & MIT) 4-20mA or Four (MIX) 4-20mA Channels 

 

Model MIX: 2-Wire,
Output Loop-Powered
(12-42DC)

Model MIT: 4-Wire,
Line/Mains-Powered
(Universal for any range between 20-375Vdc or 90-264Vac) 
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)

Lowest cost per channel signal conditioners

Switch-selectable current/voltage input types

2- and 4-channel configurations

High Density 6.35mm (0.25 inch) per channel footprint

Multi-channel signal splitter

Universal AC/DC Power Input (4-wire model)

Unit

Communication

Transmission

Power

Frequency

Option

Housing

BULLET WirelessHART Adapter by MACTek

BULLET WirelessHART Adapter Moore Industries

 

Get Product Information and Installation Tools

Platform:
WirelessHART capable network

Compliance:
Fully compliant HART 7.1 device. Backward compatible to HART 5 devices

HART
Sub-Devices:
Supports up to 8 wired HART sub-devices

 

RF Range: 235 meters outdoors, open air (normal)


RF Output Power: 10dBm

Series Loop Voltage Drop:
1.0Vdc-2.5Vdc (user-selectable in 0.5Vdc steps)

Series Loop Operating Current: 3.2mA to 25mA DC operating; Protected against over-voltage, over-current and reverse connections

External Power Operating Voltage:+7Vdc to +32Vdc; Reverse voltage protection

External Power Operating Current:

2.4GHz

Multidrop (Direct Power): 32mA DC maximum, 8 devices at 4mA DC; or 1 TCM

Multidrop (Loop Power): 24mA DC maximum, 6 devices at 4mA DC; or 1 TCM

Loop Current Monitoring Range: 3.2mA to 22mA DC, 1% Accuracy

Body:Aluminum alloy, RoHS corrosion coating, polyurethane enamel paint

Dome: Proprietary resin

Physical Connection:One, Male ½-inch NPT with internal poured seal

Electrical Connection:5 lead wires x 600mm (24-inch) long, exiting from male ½-inch NPT Opening

Ground: External earth grounding screw

Unit 

Input

Output

Power

Mounting

Features

SIY 2-Wire PC-
Programmable Signal Isolator and Converter

SIY PC-Programmable Signal Isolator and Converter Moore Industries

 

Get Product Information and Installation Tools

Sets Up in One Minute, From One Software Window

Current
Any range from
-2.5 to 55mA including:
0-20mA
4-20mA

10-50mA

Voltage
Any range from
-0.5 to 11V including:
1-5Vdc
0-10Vdc
4-20mA

 

2-Wire,
Output Loop-Powered
(10-42Vdc)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)

Field Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)

Our most versatile 2-wire signal conditioner

PC-programmable with FREE software and cable

Trim input readings and program output damping

Create 85-point custom linearization curves

Download a setup to multiple isolators

Unit 

Input

Output

Power

Mounting

Features

CPT 4-Wire PC-
Programmable Signal Isolator and Converter

CPT HLPRG PC-Programmable Signal Isolator and Converters Moore Industries

 

Get Product Information and Installation Tools

Sets Up in One Minute, From One Software Window

Current
Any range from 0 to 50mA including:
0-20mA
4-20mA
10-50mA

Voltage
Any range from 0 to 10Vdc including:
1-5Vdc
0-10Vdc

Sensor (RTD and T/C) inputs are also available. See the data sheet for details.

Sets Up in One Minute, From One Software Window

Current
Any range from 0 to 20mA including:
0-20mA

4-20mA

Voltage
Any range from 0 to 10Vdc including:
1-5Vdc

0-10Vdc

Optional Relay Output Warns of Unwanted Process Conditions
High/Low Alarms
(Failsafe or Non-Failsafe)

 

4-Wire,
Line-Powered
(24Vdc, 117Vac, 230Vac, 12Vdc or 12DC)

High-Density and RFI Resistant
Aluminum DIN-style (G-type and Top Hat rails)

Our most versatile 4-wire signal conditioner

PC-programmable with FREE software and cable

Trim input readings and program output damping

Create 85-point custom linearization curves

Download a setup to multiple isolators

Unit 

Input

Output

Power

Mounting

Features

HIT and HIX 2- and 4-Wire HART® Isolators

HIT HART Isolators Moore Industries

 

Get Product Information and Installation Tools
4-20mA
input with superimposed HART digital protocol signal
Isolates Loop, Lets HART Digital Signal "Pass Through"
4-20mA
output with superimposed HART digital protocol signal

 

HIT 4-Wire Line-Powered
(24Vdc, 117Vac, 230Vac)

HIX 2-Wire Loop-Powered
(12-42DC)

Thermoplastic DIN-style
(G-type and Top Hat rails)
Isolates the analog loop, and lets the HART digital signal “pass through” unaffected
Unit 

Input

Output

Power

Mounting

Features

SIX 2-Wire Signal Isolator, Converter, and Repeater

SIX Signal Isolator and Converter 2-Wire Moore Industries

 

Get Product Information and Installation Tools

0-20mA
4-20mA
10-50mA
0-1mA
-1 to +1mA
-10 to +1-Vdc
0.2-1Vdc
0-1Vdc
0-5Vdc
1-5Vdc
0-10Vdc
0-30Vdc

4-20mA
10-50mA

 

2-Wire,
Output Loop-Powered
(12-42Vdc)

High-Density and RFI Resistant
Aluminum DIN-style (G-type and Top Hat rails)

Fixed inputs and outputs

Non-standard input types available

Unit 

Input

Output

Power

Mounting

Features

FCT 4-Wire Field-Configurable Signal Isolator and Converter

FCT Field Configurable Signal Isolator and Converter Moore Industries

 

Get Product Information and Installation Tools
Field Configurable
0-20mA
4-20mA
0-50mA
10-50mA
0-5Vdc
1-5Vdc

0-10Vdc

Special Ranges
Field Configurable with Jumpers
0-20mA
4-20mA
0-5Vdc
1-5Vdc
0-10Vdc


Special Ranges

 

Takes any Power Supply
4-Wire, Universal Line-Powered
(accepts 22-300Vdc or 90-260Vac)

High-Density and RFI Resistant
Aluminum DIN-style (G-type and Top Hat rails)

Jumper-selectable input and output

Non-standard current/voltage inputs and outputs

Universal AC/DC power input

Powers a 2-wire transmitter (transmitter excitation)

Unit 

Input

Output

Power

Mounting

Features

FDY 2-Wire PC-
Programmable Frequency-to-DC Transmitter with Display

FDY PC-Programmable Frequency-to-DC Converter Moore Industries

 

Get Product Information and Installation Tools
Sets Up in One Minute, From One Software Window

Frequency
0.005Hz to 25KHz Ranges

Periods
40 microseconds to 200 seconds

Pulse Widths
0.2 milliseconds to 200 seconds

User-Configurable Display Shows Any Engineering Unit
4-20mA

 

2-Wire, Output Loop-Powered (12-42DC) Field-Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)

Versatile input choices

PC-programmable with FREE software and cable

Customizable display shows process status/diagnostics

Programmable moving average filter

Additional Signal Transmitters, Isolators and Converters:

ACX 2-Wire AC Current Isolator and Transmitter
SCX 2-Wire Signal Isolator and Converter
SDY 2-Wire PC Programmable Signal Isolator and Converter with Display
TMZ 4-Wire PC-Programmable MODBUS Signal Transmitter